Our Thinking / Field Notes / The Security Watch

EVOLVING SECURITY ADVISORY / DANFOSS AK-SM 800A SERIES PATH TRAVERSAL VULNERABILITY (CVE-2023-25914) ADDED TO CISA'S KNOWN EXPLOITED VULNERABILITIES CATALOGUE

Danfoss AK-SM 800A Path Traversal (CVE-2023-25914): Exploited, Fix Now

CISA added Danfoss AK-SM 800A path traversal CVE-2023-25914 and two related flaws to its exploited list on 25 November 2026. Here is who is affected, which release fixes what, and what to do first.

What matters now

Current position: High. Listed in CISA KEV on 25 November 2026. Upgrade and remove internet exposure now.

Affected versions: CVE-2023-25914 and CVE-2023-25915: AK-SM 800A below 3.3 (fixed in 3.3). CVE-2025-41450: before R4.2 (fixed in R4.2).

Observed exploitation: Exploitation confirmed by CISA's KEV listing. Known ransomware campaign use is recorded as unknown. No victims or attacker details are published by CISA.

Recommended next action: Remove internet exposure, upgrade AK-SM 800A software to the newest supported release (at least R4.2 to cover CVE-2025-41450), then check for signs of earlier compromise.

Identifiers: CVE-2023-25914, CVE-2023-25915, CVE-2025-41450

Immediate guidance

Treat this as exploited. On 25 November 2026 CISA added CVE-2023-25914 (path traversal), CVE-2023-25915 (command execution) and CVE-2025-41450 (authentication bypass) for the Danfoss AK-SM 800A Series to its Known Exploited Vulnerabilities catalogue. Software 3.3 fixes the two 2023 flaws, but CVE-2025-41450 needs R4.2 or later, so aim for the newest release Danfoss supports on your hardware. Take the controller off the internet first, upgrade it, then check it for signs of earlier compromise.

What has happened and what to do today

On 25 November 2026 CISA added three Danfoss AK-SM 800A Series vulnerabilities to its Known Exploited Vulnerabilities (KEV) catalogue, a list CISA reserves for flaws with evidence of active exploitation. The one in the title is CVE-2023-25914, a path traversal flaw in the controller's XML interface. Path traversal means a request can be crafted to escape the folder a web service is meant to serve and read other files on the underlying system. The CVE record says an attacker can use it to retrieve system files, which can lead to full system compromise.

The other two entries are CVE-2023-25915, which allows a remote attacker to run arbitrary commands, and CVE-2025-41450, an improper authentication flaw that lets an attacker generate a web report exposing internal IP addresses, usernames and store names. Both 2023 flaws are described in the CVE records as needing a logged-in user, and the 2025 flaw is an authentication bypass. Put together, that is a controller that can be reached, logged into and then abused. That chain is our reading of the entries, not something CISA has published as an attack description.

If you run these units, the order of play is: stop them being reachable from the internet, upgrade, then check whether anything got there first. The sections below follow that order.

Which systems and versions are affected

The path traversal and command execution flaws sit in the same Danfoss advisory (DSA-2023-08-01). Each flaw has its own affected range, and the fixed release you need depends on which flaws you want to close:

  • CVE-2023-25914 (path traversal) and CVE-2023-25915 (command execution): AK-SM 800A software below 3.3 is affected. Version 3.3 is the fixed release.
  • CVE-2025-41450 (improper authentication): software before R4.2 is affected. R4.2 is the fixed release. CISA's advisory describes the cause as password generation based on date and time, which is why a strong password alone does not protect an unpatched unit.
  • CVE-2025-41451 (command injection in alarm-to-mail settings) and CVE-2025-41452 (web interface denial of service) are not in the KEV list, but need R4.3.1 or later.

Reach a safe state before you upgrade

Upgrading a refrigeration controller takes planning, so start with the quick win: make the unit unreachable from places it has no business being reached from. Danfoss and CISA both say these controllers should not be exposed to the internet or given public IP addresses, and that remote access should go through a secure VPN or similarly protected network design. This is done on your firewall or router, usually by a network administrator, and needs no change to the controller itself.

  1. Look at the firewall, router and any port forwarding rules for rules that allow inbound traffic to the controller's address, including its web interface. Remove them. If a monitoring contractor needs access, move it behind a VPN you control.
  2. Check whether the controller sits on the same network as office PCs or guest Wi-Fi. If so, restrict access to it from those networks to the few machines and people that need it.
  3. From a connection outside your network, such as a mobile phone with Wi-Fi turned off, try to open your site's public address on the controller's web port. You should get no response. If the controller's page loads, the exposure is still there.

Upgrade the controller

Move to the newest release Danfoss supports for your hardware rather than stopping at 3.3. Version 3.3 closes the path traversal but leaves the later authentication flaw open. Danfoss's guidance is to move through 4.x before going to 5.0.x if you are on 3.x or older, and to read the release notes for the 5.0.x package before starting. Obtain the software package only from Danfoss's AK-SM 800A download page.

The upgrade changes the running software on a unit that may be controlling or monitoring real refrigeration and alarms. You need administrator access to the controller and, ideally, someone who knows the site's plant. Do it in a planned window, not during a delivery rush.

  1. Note the current software version and write down any manual overrides on relays and on/off inputs. Danfoss's upgrade guide says the upgrade removes them, so you will need to set them again afterwards if the plant relies on them.
  2. Export or note the controller's configuration, including user accounts and alarm-to-mail settings, so you can compare it afterwards.
  3. Load the software package through the controller's Software Upgrade function, following the Danfoss AK-SM 800A software upgrade guide. Keep power on throughout, because Danfoss warns that interrupting power during the operating system or software update can cause problems. The unit resets after loading, and during that time it is not monitoring or sending alarms, so tell whoever normally receives them.
  4. Once the unit is back, confirm the software version now shows the release you intended. Re-apply any overrides, check that alarms and data points are reporting, and test an alarm email.
  5. Change all controller passwords to strong, unique ones. Do this after the upgrade, since the authentication flaw in earlier versions means older passwords may not have been protecting the unit.

Check whether it was already exploited

CISA's two 2023 entries are flagged as needing forensic triage, which in plain terms means a quick, focused look at the device to decide whether an attacker got in before you patched. CISA's Binding Operational Directive 26-04 makes that a requirement for US federal civilian agencies only, but the sensible reading for anyone else is that the same question applies to you. No published indicators of compromise exist for these Danfoss flaws, so the checks below are general ones and a Danfoss support contact or an incident responder can help you go further.

If the controller was ever reachable from the internet while running software below the fixed releases, treat it as possibly exposed. Because the path traversal can read files on the unit, assume that anything stored on it, such as user accounts and mail settings, may have been seen.

  • Review the user accounts on the controller for any you do not recognise, and for changed privileges.
  • Look at alarm-to-mail and other notification settings for unexpected addresses or odd text in the fields. CVE-2025-41451 abuses these fields in older software, so unusual content there deserves a closer look.
  • Check firewall, VPN and internet provider logs for connections to the controller from unfamiliar addresses, and for outbound connections from the controller to anywhere unexpected.
  • If anything looks wrong, disconnect the unit from the network, keep its configuration and logs as they are, and contact Danfoss support or an incident responder before wiping or restoring it.
  • Rotate any credentials that were reused elsewhere, such as the same password used for the mail account the controller sends through.

What we know about exploitation, and what we do not

CISA's KEV listing is the evidence that exploitation has happened. The catalogue records ransomware use as unknown for all three entries, and CISA has not published who is exploiting the flaws, how many units were affected or which organisations were hit. We name no victims and you should be cautious about unsourced reports that do. CISA's own ICS advisory for the 2025 flaws still said when it was published that no public exploitation had been reported to it, so the position changed on 25 November 2026.

For federal agencies, CISA set a deadline of 28 November 2026 for the two 2023 flaws and 9 December 2026 for CVE-2025-41450. That binds those agencies only, but it shows how quickly CISA expects the two 2023 flaws to be dealt with.

A newer flaw with no fix yet

Upgrading will not close everything. On 24 November 2026 CISA published advisory ICSA-26-328-03 for CVE-2026-129713, a stack-based buffer overflow in an unauthenticated web handler affecting AK-SM8xxA software 5.4.0 and earlier. Danfoss has not released a fix, and says a 5.5.x release will address it. CISA reports no known public exploitation of it and it is not in the KEV catalogue.

Until a fix arrives, Danfoss's interim advice is to keep the units off the internet, restrict remote access with a VPN or similar protection, run every affected device in Strict Mode and use strong, unique passwords. The exposure changes you make above are the most useful protection against this one too.

Update history

We’ll keep this page updated as new information becomes available. Check back for the latest developments.

  1. Initial update: CISA added CVE-2023-25914, CVE-2023-25915 and CVE-2025-41450 for the Danfoss AK-SM 800A Series to the Known Exploited Vulnerabilities catalogue on 25 November 2026, with federal due dates of 28 November 2026 for the two 2023 flaws and 9 December 2026 for the 2025 flaw. Update source

Technical terms explained
Binding Operational Directive 26-04
A CISA directive that sets patching and triage expectations for US federal civilian agencies. It does not legally bind private organisations.
forensic triage
A rapid, focused check of a device to decide whether an attacker has exploited a vulnerability or compromised it.
Known Exploited Vulnerabilities (KEV) catalogue
CISA's list of vulnerabilities for which there is evidence of exploitation in real attacks. Listing means exploitation has been seen, not that every system is compromised.
path traversal
A flaw where a request can step outside the folder a service is meant to serve, so an attacker can read files elsewhere on the system.
Strict Mode
A Danfoss AK-SM 800A setting that Danfoss recommends enabling as an interim measure for CVE-2026-129713.